Selection guide · Fiber optics
A fiber optic patch cord, also called a fiber patch cable, is a cable terminated with connectors at both ends to connect equipment, patch panels and outlets. Choosing the right assembly involves five checks: fiber type, connectors, polish, fiber count and installation route.
How to choose · LG OPTIC families · Ordering checklist
1. Identify the fiber: OS2 or OM
The patch cord must match the installed cabling and the optical transceivers. Read the cable marking and equipment specifications: jacket colour alone is not sufficient identification.
| Category | Type | Reference |
|---|---|---|
| OS2 | Single-mode | 9/125 µm, commercial designation |
| OM1 | Multimode | 62.5/125 µm |
| OM2, OM3, OM4, OM5 | Multimode | 50/125 µm |
OM1 and OM2 have different core diameters. Although OM2 through OM5 share the same nominal diameter, their performance differs: select the category specified for the project. OM5 is wideband multimode fiber that can be used with compatible SWDM systems.
2. Check the connectors at both ends
Identify the ports to connect, for example LC–LC, LC–SC or SC–SC. The connector must match the equipment or patch panel interface. The two ends may use different connector types; check the exact product code for the required assembly.
3. Match UPC and APC correctly
UPC and APC describe different connector end-face finishes. Do not directly mate a UPC termination with an APC termination: the contact geometry is incorrect and may damage the end faces.
A UPC–APC patch cord can be appropriate when each end connects to a port with its matching polish. Check side A and side B separately: LC or SC alone does not establish compatibility.
4. Choose simplex or duplex
A simplex patch cord contains one fiber; a duplex patch cord contains two. Where transmission and reception use separate fibers, maintain the required Tx/Rx polarity. Some bidirectional interfaces use one fiber: the required count depends on the interfaces, not just the data rate.
5. Check length, jacket and protection
Measure the actual route and allow space for cable management. Check cable diameter, minimum bend radius and installation conditions in the product datasheet. Armored versions provide additional mechanical protection; armor does not automatically make a cable suitable for every outdoor location or environment.
Before connecting, inspect the end faces with suitable equipment; clean if necessary and inspect again. Even a new patch cord may have contaminated end faces.
Fiber optic patch cords: choose a family
OS2 single-mode
For single-mode equipment and cabling. The patch cord must match the fiber and interfaces used in the installation.
OM1, OM2, OM3, OM4 and OM5 multimode
For multimode cabling, choose the category specified for the project and supported by the transceivers. Link speed and reach depend on the whole system, not only on the patch cord.
- OM1 duplex patch cords
- OM2 duplex patch cords
- OM3 duplex patch cords
- OM4 duplex patch cords
- OM5 duplex patch cords
- OM1 and OM2 simplex patch cords
- OM3 and OM4 simplex patch cords
Armored patch cords
For routes requiring additional mechanical protection, explore armored fiber optic patch cords (Italian product page) and check the operating conditions specified for the exact model.
Which patch cord connects the fiber outlet to an ONT?
Check the service provider’s requirements and the ports on the outlet and ONT. Fiber type, connector and polish must match at both ends. Choose the length for the actual route while respecting the cable’s minimum bend radius.
Three practical selection examples
Connecting a switch to a patch panel in a data center
Start with the installed transceiver part number, not just the port form factor. For a 10GBASE-SR link with a duplex LC interface and OM4 cabling, select an OM4 multimode patch cord with LC at the equipment end and the connector required by the panel at the other end. Check polarity across the complete channel, including intermediate cross-connects.
As a reference, 10GBASE-SR commonly supports up to 300 m on OM3 and 400 m on OM4 under the specified link conditions. These distances apply to the complete channel; they are not independent patch cord ratings. Other data rates require a fresh check of the standard, optics and cabling.
A single-mode link between cabinets or buildings
When the optics require single-mode fiber, the patch cord must match the backbone and its terminations. Replacing a multimode patch cord with OS2 does not convert an entire link to single-mode. Include patch panel, splice and connector losses and check the environmental conditions where the patch cord will be installed.
Only one fiber is available
A simplex patch cord is appropriate only when the interfaces and architecture support transmission over a single fiber. Point-to-point BiDi links require modules with complementary transmit and receive wavelengths. Using one strand of a duplex cable does not turn a conventional duplex link into BiDi.
Understanding optical parameters
Insertion loss (IL) is the loss introduced by a component or link, expressed in dB. Under comparable measurement conditions, a lower value means less optical power is lost. Return loss (RL) describes the ratio of incident to reflected power: a higher positive value means less reflection. Reflectance may instead be expressed as a negative value, so check the quantity being specified before comparing figures.
To assess a link, include fiber attenuation at the operating wavelength, mated connections, splices and an engineering margin. The result must remain within the optical interface limits. Excessive received power can also exceed the receiver limit: select any attenuator using module specifications and measurements, rather than adding one automatically.
Jacket and bending: what to check
Jacket and protection requirements depend on the route and installation conditions. LSZH refers to smoke and halogen emission characteristics; on its own it does not establish outdoor suitability, waterproofing or a particular fire performance classification. Check applicable declarations, operating temperature and the protection required by the project for each product code.
Respect the minimum bend radius specified for the assembled cable, distinguishing installation and operating conditions where applicable. Bend-insensitive fiber does not permit arbitrary cable bends or crushing near the connector. In a rack, leave room to open drawers and manage slack without pulling on the terminations.
Common mistakes to avoid
- Choosing by colour: check the marking, product code and datasheet.
- Assuming LC means single-mode: connector shape does not identify the fiber.
- Mixing OM1 and 50/125 fiber: different core diameters can introduce loss; do not improvise a substitution.
- Expecting an OM4 patch cord to upgrade an OM2 backbone: performance depends on the complete channel.
- Connecting without inspection: check both end faces at every connection; a dust cap does not guarantee cleanliness.
Before ordering or replacing a patch cord
Record the equipment and optical module models, installed fiber, total route, connectors and polish at each end. For an existing link, keep the measurements and identify polarity before disconnecting. Use suitable diagnostic and inspection tools: never look directly into ports or fibers, and follow the manufacturer’s procedures.
Information to include in your request
- Application and equipment to connect.
- Fiber type: OS2 or the required OM category.
- Connector and polish at each end.
- Simplex or duplex configuration and required polarity.
- Length, jacket, any armor requirement and quantity.
Configuration example: OM4 duplex patch cord, LC/UPC–SC/UPC, 2 metres. This illustrates how to describe a request: availability and final specifications must be confirmed against the product code.